MNS low-voltage switch cabinet out of

Sitepath:Home > Products > Electrical > Switchgear


MNS low-voltage switch cabinet out of


Structural characteristics: 

1, the main framework for the use of C-type steel assembled, C-type material is E = 25mm mounting hole for the modulus of cold-formed from steel plate, profiles to meet a variety of structural forms, all architecture and interior partitions for galvanized passivation. 

2, the design of tight measures: in order to accommodate a smaller space more functional unit. The use of standard modular design: each of the composition of the protection, operation, conversion, control, regulation, determination, direction, such as standard cell, the user can choose according to the needs of any assembly. 

3, power distribution centers (PC): PC inside is divided into four compartments: the level of bus compartment in the rear of the cabinet; functional unit compartment in the cabinet or cabinet before the upper left; cable compartment in the cabinet before the lower part of or the right side of the counter before; control loop before the counter compartment. The level of bus functional unit compartment and compartment, cable compartment separated between the steel plate; control loop with the functional unit compartment between the compartment with flame-retardant plastic casing separated polyphenylene ether; the left side of the functional unit compartment and the right between the cable compartment separated by steel plates; main circuit and auxiliary circuit is designed to separate between the structures, instruments, lights and buttons and other components of the auxiliary circuit units are installed in the plastic dashboard. 

4, out of style motor control centers or small current momentum distribution center (MCC): MCC cabinet is divided into three compartments, the level of the rear cabinet compartment Busbar, left the Department of the former cabinet functional unit every room, right before the counter Department of cable compartment. The level of bus functional unit compartment and between compartments of plastic foam with flame-retardant board made of functional separation, with the level of the cable compartment Busbar compartment, between the functional unit compartment separated by steel plates. 

5, the drawer is divided into the type of 8E / 4 unit, 8E / 2 unit, 8E unit, 16E unit, 24E unit size five series. 

6, security features: a large number of high-strength flame-retardant engineering plastics components, effective security features to enhance the protection. 

7, high-performance technology: the main parameters reach the international advanced level. 

Main technical parameters: 

Main circuit rated voltage: AC380V, 660V; Rated Frequency: 50HZ, 60HZ; Rated insulation voltage: 600V; rated current: horizontal bus is less than 5000A, the vertical bus is less than 1000A; main busbar rated current short-term tolerance 100KA/1S, rated peak current tolerance 250KA; vertical busbar rated peak current tolerance 90KA.

Prev: GCS AC low-voltage switch cabinet out of Next:XL Series power distribution box